Precautions for installation and use of regulator valve

Matters needing attention for installation and use of regulator valve:

New design, installation of the control system, in order to ensure that the regulator valve in the start up can work normally, and make the system safe operation, before the installation of the new valve, should first check whether the nameplate on the valve is consistent with the design requirements. The following projects should also be debugged. Basic error limit; Full stroke deviation; Back to the poor; Dead zone; Leakage volume (in a demanding situation).

If it is the original system control valve overhaul, in addition to the above check, should also old valve stuffing box and joints and other parts of the sealing inspection. Regulator valve in the field of use, many often is not caused by the quality of the regulator itself, but the improper installation of the regulator valve caused by, such as the installation environment, installation position and direction of improper or pipeline is not clean and other reasons. Therefore, the electric control valve should pay attention to the following aspects in the installation and use:  

(1) the control valve belongs to the field instrument, the environmental temperature should be in the range of -25 ~ 60℃, relative humidity ≤95%. If it is installed in the open air or high temperature occasions, should take waterproof, cooling measures. In the source of the place to be away from the source of vibration or increase anti-vibration measures.

(2) the regulating valve should be installed vertically in general, under special circumstances can be tilted, such as the tilt Angle is very big or the valve itself weight is too big when the valve should be added support protection.

(3) the pipeline for installing the regulator valve should not be too high from the ground or the floor. When the height of the pipeline is greater than 2 m, the platform should be set as far as possible to facilitate the operation of the handwheel and maintenance. (4) before the installation of the regulator valve, the pipeline shall be cleaned to remove dirt and welding slag. After installation, in order to ensure that impurities do not remain in the body, the valve should be cleaned again, that is, all the valves should be opened when the media is in, so as to avoid impurities stuck. After using the handwheel mechanism, should be restored to the original neutral position.

(5) in order to enable the regulator to continue the production process in the case of failure or maintenance, the regulator shall be provided with a bypass pipeline.

At the same time, special attention should be paid to whether the installation position of the regulator conforms to the requirements of the process.

(6) the electric part of the electric control valve shall be installed according to the construction requirements of the relevant electrical equipment. If the flameproof product is used, it shall be installed according to the requirements of "installation code of electrical equipment in explosive dangerous places". Such as the scene copper-clad SBH type or other six or eight core, the outer diameter is about 11.3 mm Φ rubber cable installation. In the use of maintenance, in the explosive places are prohibited to open the electricity cover maintenance and the explosion-proof surface for pry. At the same time, do not break or scratch the flameproof surface in the process of disassembly and installation, and restore to the original flameproof required state after maintenance.

(7) the reducer of the actuator should pay attention to oil lubrication after repair, low speed motor generally do not 

Analysis of common fault locations and causes

The working performance of the regulating valve will directly affect the working quality of the whole regulating system. Because the regulating valve is in direct contact with the adjusted medium on the spot, the working environment is very bad, so it is easy to produce a variety of faults. In the production process, in addition to the troubleshooting at any time, but also must carry out regular maintenance and regular maintenance. Especially for the use of the environment is particularly bad control valve, more attention should be paid to the maintenance and regular maintenance.

Different types of regulator, its failure and its causes are not the same. Taking the direct stroke electric control valve produced by * instrument general factory as an example, the general failure and maintenance method of electric control valve are illustrated.

2.1 servo amplifier

When the servo amplifier works normally:

(1) when there is no input signal, there should be no output voltage.

(2) open loop dead zone current acuities were 160 mu (Ⅱ type is 100 mu).

(3)輸入信號>240 μA(Ⅱ型為150 μA)時,輸出負載電壓為205~220VAC。

(4) the output voltage is basically symmetrical.

If the servo amplifier is not working properly, the following situations may occur in each part:

(1) magnetic preamplifier

When there is no signal input, the output of the double-beat magnetic amplifier can be adjusted to zero through the potentiometer W101. If it cannot be set to zero, it may be:

A. Transformer W101 is out of welding or damaged.

B, resistors R110, R111 and electrolytic capacitors C101, C102 are welded or unwelded.

C, diode D105 ~ D108 virtual welding or damage.

D. abnormal deviation current.

E. Asymmetric ac winding.

(2) there is an input signal, but no output or output asymmetry may be:

A. The voltage at the secondary end of the ac winding current supplied by transformer B301 is asymmetric.

The resistance values of B and R110 and R111 have changed, and the electrolytic capacitor C110 and C111 are damaged.

C. Ac excitation winding short circuit.

D, diode D105 ~ D108 have individual tube damage or virtual welding.

(2) when the flip-flop has input, one side of the flip-flop should have an impulse signal on the oscilloscope screen. If the polarity of the input signal is changed, the other side of the flip-flop should have an impulse signal. The number and amplitude of the two sets of trigger pulses should be basically the same. Otherwise, there are several situations.

There is no input signal (the pre-magnetic amplifier is in normal working state), and there is a trigger pulse at the output end, which may be:

A. The triode on the side with triggered pulse output is damaged, or it is extremely virtual welding of c and e.

B, resistance R204, R205, R208, R209 resistance values changed.

There is an input signal and no trigger pulse at the output terminal, which may be:

A. The triode on the side without output pulse and the single-junction tube are damaged.

B. Primary or secondary circuit failure or short circuit of the pulse transformer on the side without output pulse.

C. The diode (D207 or D208) on the side without output pulse is short-circuited.

(3) abnormal output trigger pulse has the following phenomena:

A. When there is no signal, the two sets of triggers have pulse output, which is normal after the signal is added, which may be the virtual welding of electrolytic capacitor C202 or C203.

B. The output of both sides of the trigger is normal at the beginning. After working for a period of time, the output pulse gradually disappears.

C. Positive and negative pulses appear in the output, which may be the breakdown or virtual welding of diode D207 and D208.

(3) after the above inspection and maintenance, the servo amplifier should work normally when the control circuit is fault-free. Otherwise, there are two situations:

When there is no input signal, the output voltage (the voltage is close to 220VAC) may be:

A. SCR SCR1 and SCR2 are damaged.

B. Capacitors C301 and C302 are broken down.

When there is an input signal, there is no output signal or the output voltage is too low, then it may be:

A, diode D301 ~ D308 have been broken.

B. SCR SCR1 and SCR2 are damaged.

2.2 the regulator

When 4 ~ 20 mA signal is input, the regulating valve stem can move up and down freely in the rated stroke with the change of signal. If normal operation is not possible, the following faults may occur:

Operating handwheel paresthesia

A. It feels too light, maybe the handwheel pin has fallen off or broken.

B. It feels too heavy or can't swing. There is a foreign body stuck in the reducer; Spool and bushing or stuck with seat; The stem is severely bent.

Input 4 ~ 20 mA signal, the regulating valve does not work.

A. wrong connection of the system.

B. CD of motor splitter capacitor is damaged.

C. Open motor wiring.

D. Spool falls off or stem breaks (at this time, actuator has action)

Input 4 ~ 20 mA signal, the regulator valve can not complete the rated stroke.

A. the position of the differential transformer is not adjusted.

B, diode D701 ~ D712 has individual damage.

C. Triode BG701 is damaged.

(4) other faults in field use.

Valve vibration, call.

A. If the sensitivity is adjusted too high, the actuator will oscillate.

B. The fluid pressure changes too much and the actuator lacks thrust.

C, the choice of the regulating valve is large, the valve often in a small opening work.

D. The flow direction of the medium is consistent with the closing direction of the valve.

E, nearby other source impact, support instability.

F, spool and bushing wear seriously.

The valve is slow.

A. The viscosity of the medium is too large, resulting in blockage or coking.

B, the packing aging, packing pressure is too tight.

Large amount of leakage.

A. Valve core or seat is corroded and worn.

B. Loose seat or corroded thread.

C. There is a foreign body on the seat and spool.

D. The starting point (electric open type) or ending point (electric closed type) of the valve is not adjusted.

(4) packing and upper and lower cover joints leakage.

A. The packing gland is not pressed tight.

B. teflon packing aging and deterioration.

C. Stem damage.

D. the tightening nut is loose.

E. damaged gasket.The correct use and maintenance of the electric control valve can not only improve the adjustability of the process control, but also increase the service life of the electric control valve, which has considerable economic benefits to the energy saving and consumption reduction of enterprises.


主站蜘蛛池模板: 上海画册设计-上海宣传册设计-产品手册设计-企业画册设计公司 | 亚洲一区日韩一区欧美一区a,中文字幕乱妇无码AV在线,欧美日韩免费在线观看,国产精品一区二区三区免费,日韩精品免费一线在线观看,日韩一本在线,国产呦精品一区二区三区下载,国产日韩精品一区二区在线观看,欧美日韩高清一区二区三区,日韩在线免费观看视频,欧美日韩一区在线观看 | 山东邹平华强无纺布有限公司 | 暖家乐散热器_天津市暖家乐金属制品有限公司| 江苏鹤心食品有限公司-茶叶_果浆果酱_固体饮料 | 宁波管道安装_宁波工业冷风机_宁波冷风机厂家_宁波厂房通风降温_「浙江甬风机电」 | 通道闸-人行通道闸|通道闸机系统厂家-深圳伊帕克智能科技有限公司 | 纸袋胶-糊盒胶-礼盒胶-裱纸胶-水性喷胶-东莞市美好化工有限公司 纸袋机|多层纸袋机|高速纸袋机|无锡市天天友情机械有限公司 | 青州东威机械有限公司,洗沙机,脱水筛、细沙回收机,淘金设备,洗石机,砂石分离机,筛沙机,采沙船,清淤船,破碎制砂机,海沙淡化设备 | 苏州探测器清洗_烟感探头清洗_感烟探测器维修清洗_火灾探测器清洗报价/价格_进口国产消防设备清洗_江苏智淼探测器清洗厂家- | 冷缩电缆附件_热缩电缆附件-乐清安尚电气有限公司 | 人防信号控制箱厂家-液位控制器价格-信号灯箱批发厂家-消声加热器-鼎兴自控 | 上海海外置业展_2024海外置业移民留学展_4月5-7日_企业参展处/免费领门票 | 连云港海盛石英科技有限公司 | 西安男科医院_陕西男性专科医院_陕西老医协生殖医学医院【官网】 | 全国产品维权打假真伪验证系统-石家庄市海略科技有限公司官方网站 | 铅板,防辐射铅板,医用铅板,保定美伦有色金属有限公司 | 江门市金环电器有限公司 | 河南反渗透设备-河南EDI超纯水设备-郑州纯净水设备-郑州友邦水处理设备有限公司 | 青州市昌达机械设备有限公司_洗石机-洗砂机-筛沙机-砂石分离机-洗轮机-制砂机 | 上海中泉泵业制造有限公司-柴油机泵,一体化泵站,柴油机消防泵,泵站,预制一体化泵站 | 浙江云野科技有限公司_智慧旅游规划_智慧景区管理系统_全域旅游解决方案-云野科技旅游大数据管理平台 | 山东汇河环保科技集团有限公司,水囊水袋,水罐,油囊,预压水袋,吊重水袋_山东汇河环保科技集团有限公司,水囊水袋,水罐,油囊,预压水袋,吊重水袋 | 上海钧尚电器有限公司 - Faulhaber电机 AMETEK pittman电机 AMETEK ROTRON军用航空风机 Exlar电动缸 MAE电机 MCG电机 CP电动工具 马头工具 AMCI驱动器 直流电机 减速箱 直流伺服电机,无刷电机,直线电机 直流防爆电机 防爆电机 汽车助力转向电机 EPS电机 faulhaber motor faulhaber gearbox NANOTEC电机 ELWOOD电机 PHYTRON电机 EXLAR伺服电动缸 高力矩、高性能直流电机,音圈电机,风机,直流风机,航空风机 | 轴流消防排烟风机,排烟防火阀厂家,铝合金百叶风口-德州正邦通风设备有限公司 | 气体检测仪,多功能气体检测仪,四合一检测仪,氯气检测仪,有机挥发气体检测仪,气体报警器-南京诺邦电子科技有限公司 | 临沂网站建设,临沂网站制作,临沂网络公司,临沂小程序开发,临沂网站设计,沂水网站建设,沂南网站建设,蒙阴网站建设,平邑网站建设,费县网站建设,兰陵网站建设,郯城网站建设,临沭网站建设,莒南网站建设,兰山网络公司 | 气瓶探伤设备-气瓶在线离线无损探伤检测系统-中高低压力容器超声波自动探伤设备-山科飞泰 | 指纹锁_智能锁_指纹密码锁_智能锁十大品牌_智能门锁厂家-深圳市豪力士智能科技有限公司 | 上海舜华新能源系统有限公司_官网 | 上海浩斌信息科技有限公司RFID读写器,IC卡读卡器,手持机,数据采集终端,电力仓库管理软件开发,固定资产软件,纱管标签,试剂管理,RFID试剂柜,档案管理,档案柜,智能货架 | 自动封箱机_纸箱封箱机_封箱机厂家-青岛百高包装器材有限公司 | 无塔供水_无塔供水设备_全自动_石家庄工泉水处理设备有限公司_家用无塔供水器 | 莱湾科技-智能会议室|多功能|多媒体|音视频|无纸化|远程视频会议室运维 | 思沃普智能会议预约管理系统-视频会议管理-信息发布-访客管理-会议运维-会议支持-工位管理系统 | 兰州职业学校-新华互联网学校咨询平台中心 | 石家庄装修设计_别墅装修装饰公司-金舍装饰官网| 温湿度变送器_pm2.5传感器_湿敏电阻_二氧化碳传感器_甲醛传感器-美特瑞科技 | 思达测试|山东思达高科机械设备有限公司 | 真空烘箱-高低温试验箱-防爆烘箱-防爆高低温试验箱-老化房-恒温恒湿箱-高低温试验箱-高低温冲击试验箱厂家—上海标承实验仪器有限公司 | 提供技术支持-TXC晶振-晶振厂家-32.768K,石英晶体振荡器厂家销售-NDK振荡器正规代理商 |